Our known compact control unit SHEV® with its versions 3A and 6A is now compatible with Simon Link®. Until now settings for SHEV®, especially for the ventilation part, have been adjustable only by the DIP switches. In case of longer time ranges (e.g. automatic ventilation close) the technician on site had to wait for the whole time. Our software for parametrisation called Simon Link, known for the setup of force and stroke at the actuator technology , offers now a multitude of settings for the compact control panel type SHEV®. Beside the known settings for ventilation you will find at Simon Link now the possibility for switching off the retriggering, use of the maintenance counter (perfect for the technician on site), change of the start up delay for the motor channels and maximum time for powering the motor channels in case of main failure (battery mode).
Features overview:
- Readout different cycle counters (e.g. Missing main failure, Powering of the actuators in OPEN and CLOSE direction, ALARM mode at the different alarm lines, ...)
- Readout of the current status with further informations in case of an error
- Parametrisation of following values:
- Gap ventilation: you can set the value in seconds directly on site without waiting
- Automatic ventilation close: you can set the value in minutes directly on site without waiting
- Battery powering: Powering of the actuators for ventilation in case of battery mode
- Switching off retriggering (set to ON in case of standard)
- Start up delay: After ALARM the actuators just start after a definite delay
- Maintenance cycle counter: After the set time (e.g. 365 days) the control panels shows error (yellow LED) and this error can just be resetted by Simon Link®