The Fire PROtec² S200 C2 from SIMON PROtec is an automatic smoke-proof curtain in accordance with EN 16034, designed specifically for use as a textile smoke protection closure. With its S200 classification, the curtain provides tested smoke leakage performance at ambient temperature and at elevated temperatures of 200 °C.
Thanks to its compact design and flexible mounting options, the smoke curtain can be integrated into different building designs without requiring much space. The Fire PROtec² S200 C2 combines reliable smoke protection with a discreet appearance and easy installation.
S200 - Tested smoke leakage performance at 200 °C
The S200 classification (smoke-proof) confirms that the Fire PROtec² S200 C2 meets the requirements for smoke leakage performance even at an elevated temperature of 200 °C. The smoke retarding curtain has been tested and classified accordingly.
In addition, the automatic smoke retarding curtain has a C2 classification for its self-closing properties.
This makes the Fire PROtec² S200 C2 suitable for buildings and areas where a smoke-proof closure is required.
Versatile applications for smoke-proof curtains
The Fire PROtec² S200 C2 can be mounted either on the wall or within a reveal. Its space-saving design makes the smoke-proof curtain suitable for installation locations where only limited space is available for the housing.
Typical applications include:
The compact design allows the smoke-proof curtain to be integrated discreetly into the building architecture.
Head box dimensions (W × H):
For unwinding lengths below 3,000 mm: 150 × 182 mm
For unwinding lengths of 3,000 mm and above: 180 × 212 mm
Easy Installation
The automatic Fire PROtec² S200 C2 smoke curtain is designed for quick and easy installation. A key advantage is the Snap-in mechanism, which allows the pre-assembled roller unit to be inserted into the housing quickly and easily.
This reduces installation work and makes mounting and commissioning of the system easier.
Different control options with the approved RZ-24 hold-open system are available for the smoke-proof curtain. Depending on the requirements, the system can be equipped with or without an emergency power supply and with an EMERGENCY OPEN function.
Smoke-proof curtain for up to 9 m²
The Fire PROtec² S200 C2 can be used for openings with a total area of up to 9 m².
This makes the smoke-proof curtain a compact and flexible solution for different installation situations where a textile smoke protection closure with S200 classification is required.
| Matchcode | FSV2-S200-C2 |
| Article name | Smoke curtain Fire PROtec² - S200 C2 |
| Part number | FSV2 3004 |
| Classification | CE marking in accordance with EN 16034 with classification S200 C2 in accordance with DIN EN 13501-2 (tested to EN 1634-3) |
| Fabric | Wire-reinforced glass filament fabric with silicone coating on both sides; non-combustible in accordance with A2 by DIN 4102-1. |
| Unwind | descending by gravity (fail safe) |
| Rewind | planetary gear drive, 24 V DC, 3 A with electronic overload cut-off; roll shaft-integrated |
| System installation | Reveal and wall-mounting with appropriate, approved mounting material |
| System size | max. total surface 9 m² |
| Housing | Head box (W x H): Sheet steel 1.5 mm (for roll-up lengths ≤ 3000 mm (W x H): 150 x 182 mm; for roll-up lengths ≥ 3000 mm (W x H): 180 x 212 mm); Side guides (W x H): Sheet steel 2 mm (58 x 95 mm) |
| Bottom Bar | Steel 2 mm with integrated springs and round steel in fabric bag for gravity fail-safe |
| Housing type | |
| Housing width | 150 |
| Housing height | 182 |
Fire protection curtain Fire PROtec² - S200 C2
Fire PROtec² S200 C2 according to DIN EN 16034
System size: max. surface 9 m²
Head-box length: ___ mm
Clear width: ___ mm
Total height: ___ mm
Unroll length / Clear height: ___ mm
Manufacturer:
SIMON PROtec Systems GmbH | Medienstraße 8 | D-94036 Passau
Type: Fire curtain Fire PROtec² Sa4 C0
Article number: FSV2 3004
WEEE Reg. No.: DE 97535049
Brochure FSV + RSV | Brochure about the fire protection curtains and smoke protection curtains |
Declaration of Performance FireProtec² Sa4/S200 (Draft) | Declaration of Performance |
Project data Fire PROtec² Sa4/S200 | Project data |
Safety instructions and warranty conditions | Safety instructions and warranty conditions |