The Fire PROtec² Sa4 C2 from SIMON PROtec is an automatic smoke-tight curtain in accordance with EN 16034. Its smoke-tight design on all four sides provides a reliable textile smoke protection solution for buildings.
The compact smoke curtain can be installed in different locations and requires little space. With its Sa4 C2 classification, the system is suitable for areas where a smoke-tight closure with self-closing properties is required.
Sa4 C2 - smoke-tight on all four sides at ambient temperature
The Sa4 classification (smoke-tight) confirms that the Fire PROtec² Sa4 C2 meets the specified leakage requirements on all four sides at ambient temperature.
In addition, the smoke retarding curtain has a C2 classification, which specifies its tested self-closing capability.
The Fire PROtec² Sa4 C2 is therefore suitable for building applications where a smoke-tight curtain is required as a smoke protection closure.
Smoke-tight protection for different building areas
Thanks to its compact design, the Fire PROtec² Sa4 C2 can also be used where installation space is limited. The automatic smoke curtain is suitable for both wall mounting and reveal mounting. It can be integrated discreetly into existing building architecture.
The smoke-tight curtain is suitable for various applications, including:
Thanks to its small housing dimensions, the Fire PROtec² Sa4 C2 is particularly suitable for projects where a space-saving smoke protection solution is required.
Housing dimensions (W × H):
For unwinding lengths below 3,000 mm: 150 × 182 mm
For unwinding lengths of 3,000 mm and above: 180 × 212 mm
Quick installation with pre-assembled components
The Fire PROtec² Sa4 C2 is designed for easy installation and commissioning. The pre-assembled roller unit can be inserted quickly and easily into the housing using the proven Snap-in mechanism.
This installation-friendly design saves time and reduces installation work.
Different control options with the approved RZ-24 hold-open system are available for the automatic smoke-tight curtain. Depending on the requirements, the system can be equipped with or without an emergency power supply and with an EMERGENCY OPEN function.
Smoke-tight curtain for large openings
The Fire PROtec² Sa4 C2 can be used as a smoke-tight closure for system sizes of up to 4,595 × 4,495 mm (W × H).
This makes the automatic smoke retarding curtain suitable for larger building openings where a smoke-tight design on all four sides is required.
| Matchcode | FSV2-Sa4-C2 |
| Article name | Smoke curtain Fire PROtec² - Sa4 C2 |
| Part number | FSV2 3003 |
| Classification | CE marking in accordance with EN 16034 with classification Sa4 C2 in accordance with DIN EN 13501-2 (tested to EN 1634-3) |
| Fabric | Wire-reinforced glass filament fabric with silicone coating on both sides; non-combustible in accordance with A2 by DIN 4102-1. |
| Unwind | descending by gravity (fail safe) |
| Rewind | planetary gear drive, 24 V DC, 3 A with electronic overload cut-off; roll shaft-integrated |
| System installation | Reveal and wall-mounting with appropriate, approved mounting material |
| System size | max. 4.595 x 4.495 mm (WxH) |
| Housing | Head box (W x H): Sheet steel 1.5 mm (for roll-up lengths ≤ 3000 mm (W x H): 150 x 182 mm; for roll-up lengths ≥ 3000 mm (W x H): 180 x 212 mm); Side guides (W x H): Sheet steel 2 mm (58 x 95 mm) |
| Bottom Bar | Steel 2 mm with integrated springs and round steel in fabric bag for gravity fail-safe |
| Housing type | |
| Housing width | 150 |
| Housing height | 182 |
Fire protection curtain Fire PROtec² - Sa4 C2
Fire PROtec² Sa4 C2 according to DIN EN 16034
System size: max. 4,595 x 4,495 mm (WxH)
Head-box length: ___ mm
Clear width: ___ mm
Total height: ___ mm
Unroll length / Clear height: ___ mm
Manufacturer:
SIMON PROtec Systems GmbH | Medienstraße 8 | D-94036 Passau
Type: Fire curtain Fire PROtec² Sa4 C2
Article number: FSV2 3003
WEEE Reg. No.: DE 97535049